David Iszchak, Technical Trainer at Vokèra, regularly delivers fault-finding training for installers. Whether the boiler is a decades-old heat-only model or the latest condensing combi, he says the diagnostic sequence is fundamentally the same. Here, he sets out five key steps for efficient, cost-effective and safe fault finding.
1. Do your homework before you arrive
The job starts before you see the boiler. During the initial phone call with the customer, ask plenty of questions, even ones that sound obvious, and establish whether it’s actually broken, since some customers confuse a service call with a repair.
Check whether it’s on a credit meter that may just need topping up. Listen if the customer thinks they know the cause but never take it at face value — they may have self-diagnosed online and be wrong. Always verify with your own checks.
If you have been booked in for a routine service and the boiler is switched off on arrival, fire it up and confirm both heating and hot water are working before you begin, otherwise a customer could claim it was working beforehand if it fails to start once you have finished.
2. Don’t ignore the simple stuff
Once on site and before any diagnostic work begins, carry out your basic checks; confirm there is fuel, power and water in the system. Check the emergency control valve, flue, combustion air supply and pressure relief valve; is it dripping?
It’s also worth taking a moment to visually inspect the boiler and its surroundings before you go any further. Look for scorching, corrosion, staining or any sign of a leak. You’re working when you walk up the path.
Before any remedial work is carried out, safely isolate the boiler. Remember that standby is not the same as off; isolation should always be at the mains and confirmed. Only then is it safe to carry out internal inspection and work. 230V can hurt, but newer boilers may have 325VDC, which should be treated with even greater caution.
3. Understanding the operating sequence
This is the simplest and most effective fault-finding method available to an installer, and it works whatever the make or age of the boiler. Once you establish where the boiler is stopping in the sequence, you know where to start looking.
Create demand and check the relevant components; on a combi, this may be the flow device, flow switch or turbine; on the heating side, linking out the switching terminals can help confirm whether the fault lies with the controls, such as flat batteries in an RF room thermostat.
Once demand is established, the PCB checks the safety controls, including the boiler thermostat, overheat protection, system pressure and condensate sensor, before allowing ignition.
On premix (Band A) boilers, the fan starts immediately; on Band B and earlier models, the PCB first confirms the air pressure switch is in the correct position before starting the fan, then checks that airflow closes the switch, confirming adequate airflow before ignition.
Combis fire at 100% output immediately to maximise hot water delivery, while heat-only and system boilers typically fire at 60–70% for the first 15 minutes for improved efficiency. For an accurate gas rate reading, place the boiler in flue gas analysis (FGA) mode and run it at maximum output.
4. Check the system pressure
With a call for heating, the PCB monitors the flow and return thermistors; the temperature change tells it whether the pump is running and if the diverter valve is correctly positioned.
Vokèra boilers have no flow switches on the primary circuit, so this temperature monitoring is how correct operation is confirmed. A pressure transducer or switch will confirm there is enough system pressure to operate safely (a pressure transducer has the advantage of warning the customer with a fault code if pressure rises too high, where a switch gives no such warning).
To check the pressure gauge itself, cycle the pump on and off; the needle should move up and down slightly. If it jumps around erratically as the system warms, this can indicate insufficient charge in the expansion vessel, and dirt lodged in the gauge can also cause false readings, so this is worth checking closely after any system flush or refill.
5. Let the multimeter do the talking
A multimeter is one of the most valuable, diagnostic tools available. Replacing components without testing them first is one of the most common and costly mistakes in fault finding. Most components can be tested safely with the power off, by measuring resistance in ohms; always disconnect a component when testing and test the cables later if necessary.
Choose a meter that also measures in Hertz, since pumps, fans and flow turbines send frequency signals to the PCB.
There are two types of fans; single speed and modulating. With a single speed fan, if voltage is present, the neutral is sound, yet it is still not turning, the fan itself is likely to be at fault.
Modulating fans are different as they contain their own PCB, so deciding whether it’s an onboard or offboard problem is the interesting part of the job. Extra caution is needed on newer models, which may use 325VDC fans; reinforcing the importance of safe isolation before any internal checks are carried out.
Mechanical switches should always be tested multiple times with the spade connectors disconnected; a single pass is not enough to trust the result, and resistance should read no more than 3–5 ohms.
Once the sequence is running correctly, don’t skip the FGA: a calibrated analyser checking the CO/CO2 ratio confirms safe, efficient combustion, and it’s a requirement under the Gas Safety (Installation and Use) Regulations, not an optional extra.
Fault finding rewards method over guesswork. Installers who follow the sequence and trust their test equipment over assumptions will diagnose faster, avoid needless parts replacement, and build customer confidence in a repair-first approach.
Vokèra runs regular fault-finding training courses for installers looking to build on these fundamentals.